Thermal Energy Storage: full storage profile
hour 10 to hour 19
Thermal energy storage (TES) design data — chilled water density vs temperature, full/partial storage 24-hour sizing profiles, design-day ice storage leaving chilled temperature data, TES operating modes, and instrumentation accuracy requirements per ASHRAE Handbook HVAC Systems and Equipment 2020 Chapter 50
| category | item id | chiller output tons (tons) | cooling load tons (tons) | hour (h) | tes charge ton hours (ton-h) |
|---|---|---|---|---|---|
| full storage profile | hour 10 | 2,222 | 2,176 | 10 | 12,657 |
| full storage profile | hour 11 | 2,222 | 2,508 | 11 | 12,371 |
| full storage profile | hour 12 | 2,206 | 2,668 | 12 | 11,909 |
| full storage profile | hour 13 | 0 | 2,833 | 13 | 9,076 |
| full storage profile | hour 14 | 0 | 2,900 | 14 | 6,176 |
| full storage profile | hour 15 | 0 | 2,900 | 15 | 3,276 |
| full storage profile | hour 16 | 0 | 2,784 | 16 | 492 |
| full storage profile | hour 17 | 2,222 | 2,588 | 17 | 126 |
| full storage profile | hour 18 | 2,222 | 2,348 | 18 | 0 |
| full storage profile | hour 19 | 2,222 | 2,077 | 19 | 145 |