Thermal energy storage (TES) design data — chilled water density vs temperature, full/partial storage 24-hour sizing profiles, design-day ice storage leaving chilled temperature data, TES operating modes, and instrumentation accuracy requirements per ASHRAE Handbook HVAC Systems and Equipment 2020 Chapter 50

Mechanical Engineeringcategory: design day ice lct9 rowsPage 2 of 3
categoryitem idchiller lct F (F)chiller output tons (tons)cooling load tons (tons)hour (h)primary return temp F (F)storage inventory ton hours (ton-h)storage lct F (F)
design day ice lcthour 1145.25007001153.22,90032.5
design day ice lcthour 124650075012542,65032.9
design day ice lcthour 1346.85008001354.82,35033.3
design day ice lcthour 1447.65008501455.62,00034
design day ice lcthour 1549.25009501557.21,55036.6
design day ice lcthour 16505001,00016581,05038.6
design day ice lcthour 1749.25009501757.260039.1
design day ice lcthour 1847.65008501855.625039
design day ice lcthour 19465007501954042