Thermal Energy Storage: chilled water density
temp 50 to temp 68
Thermal energy storage (TES) design data — chilled water density vs temperature, full/partial storage 24-hour sizing profiles, design-day ice storage leaving chilled temperature data, TES operating modes, and instrumentation accuracy requirements per ASHRAE Handbook HVAC Systems and Equipment 2020 Chapter 50
| category | item id | density lb per ft3 (lb/ft3) | temperature F (F) |
|---|---|---|---|
| chilled water density | temp 50 | 62.411 | 50 |
| chilled water density | temp 52 | 62.404 | 52 |
| chilled water density | temp 54 | 62.396 | 54 |
| chilled water density | temp 56 | 62.387 | 56 |
| chilled water density | temp 58 | 62.378 | 58 |
| chilled water density | temp 60 | 62.368 | 60 |
| chilled water density | temp 62 | 62.357 | 62 |
| chilled water density | temp 64 | 62.344 | 64 |
| chilled water density | temp 66 | 62.331 | 66 |
| chilled water density | temp 68 | 62.316 | 68 |