API Standard 2000 (7th Ed 2014) tank venting requirements — normal thermal inbreathing/outbreathing SCFH by tank volume (100–180,000 bbl), pump-in/pump-out liquid movement venting rates, emergency fire-case venting by wetted area (100–2800 ft2), flash point and latitude correction factors, insulation credits, conservation vent set pressure/vacuum settings, and vent type selection guidance for atmospheric and low-pressure fixed-roof storage tanks

Chemical Engineeringventing_scenario: normal_thermal3 rows
venting scenariorecord idnotesparameter categorytank volume bbl (bbl)thermal inbreathing scfh (ft^3/hr)thermal outbreathing scfh nonvolatile (ft^3/hr)thermal outbreathing scfh volatile (ft^3/hr)
normal_thermalthermal_10000bblInbreathing = 10,000 SCFH; outbreathing non-volatile = 6,000 SCFH; volatile = 10,000 SCFHthermal_breathing10,00010,0006,00010,000
normal_thermalthermal_1000bblInbreathing = 1000 SCFH; outbreathing non-volatile = 600 SCFH (60%); volatile = 1000 SCFH (100%)thermal_breathing1,0001,0006001,000
normal_thermalthermal_100bblNormal thermal inbreathing = 1 SCFH/bbl for tanks <= 20,000 bbl; outbreathing for non-volatile (FP>=100F) = 60% of inbreathing; for volatile (FP<100F) = 100% of inbreathingthermal_breathing10010060100