Physical — Vertiv STS2 1200 1850A

Manufacturer Model
Vertiv STS2 1200 1850A
Spec Type
Physical
Audible Noise Dba (dBA)
72
Cooling Type
Forced Air
Depth in (in)
35.6
Depth MM (mm)
905
Device Type
STS
Fan Redundancy
4 Fans (loss of 1 Does Not Affect operation)
Height in (in)
88
Height MM (mm)
2,235
Humidity Pct Max (%)
90
Manufacturer
Vertiv
Model
Liebert STS2 1200-1850A
Operating Temp Max C (degC)
40
Operating Temp Min C (degC)
0
Phases
3
Storage Temp Max C (degC)
55
Storage Temp Min C (degC)
-20
Voltage V
380/400/415/480/575/600
Voltage V List
380,400,415,480,575,600
Voltage V Max
600
Voltage V Min
380
Weight Kg (kg)
649
Weight Lb (lb)
1,430
Width in (in)
25.7
Width MM (mm)
654