Sample data from Engineering Database — 375 reference tables, deterministic calculators, and Engineering AI. Sign up free

Refrigerants: R507A

0.8638 to 1.9602

Refrigerant saturation property tables — saturation pressures, temperatures, enthalpies, entropies, and specific volumes for 40 refrigerants (R134a, R410A, R404A, R22, R717/ammonia, R744/CO2, HFOs, natural refrigerants, cryogenics, etc.)

Mechanical Engineeringrefrigerant: R507A10 rowsPage 2 of 7
refrigerantpressure barhf kJ kg (kJ/kg)hfg kJ kg (kJ/kg)hg kJ kg (kJ/kg)sf kJ kgK (kJ/kgK)sfg kJ kgK (kJ/kgK)sg kJ kgK (kJ/kgK)temp C (C)temp F (F)vf m3 kg (m3/kg)vg m3 kg (m3/kg)
R507A0.8638135.03199.02334.050.73950.89191.6314-50-580.0007540.20801
R507A0.9533137.51197.74335.250.75050.87831.6288-48-54.40.0007570.1896
R507A1.0499139.99196.46336.450.76150.86491.6264-46-50.80.0007610.17313
R507A1.1541142.48195.17337.650.77240.85171.6241-44-47.20.0007640.15836
R507A1.2662144.99193.85338.840.78320.83871.6219-42-43.60.0007680.1451
R507A1.3867147.49192.54340.030.7940.82581.6198-40-400.0007720.13317
R507A1.5159150.01191.2341.210.80470.81311.6178-38-36.40.0007760.1224
R507A1.6542152.54189.84342.380.81530.80061.6159-36-32.80.000780.11268
R507A1.8022155.08188.47343.550.8260.78811.6141-34-29.20.0007840.10388
R507A1.9602157.63187.09344.720.83650.77581.6123-32-25.60.0007880.0959