Rack Infrastructure Specs: Tate DirectAire Floor

airflow kw at 25pa no damper to floor rolling load 10passes

Datacenter rack infrastructure specifications — OCP Open Rack V3 frame and busbar dimensions, OCP BBU module and shelf electrical parameters, OCP 48V onboard PSU efficiency and peak load profiles, GE OCP 48V power shelf rectifier efficiency comparison, and Tate raised floor system load and airflow performance data

Electrical Engineeringcomponent type: Tate DirectAire Floor10 rowsPage 2 of 3
component typespec parameterparameter nametest conditionunitvalue
Tate DirectAire Floorairflow kw at 25pa no damperDirectAire cooling capacity without damper at 25 PakW/rack19.1
Tate DirectAire Floorairflow kw at 25pa with obdDirectAire cooling capacity with OBD damper at 25 PakW/rack17.2
Tate DirectAire Floorairflow kw at 5pa no damperDirectAire cooling capacity without damper at 5 PakW/rack8.5
Tate DirectAire Floorairflow kw at 5pa with obdDirectAire cooling capacity with OBD damper at 5 PakW/rack7.3
Tate DirectAire Floorfloor airflow capture indexDirectAire airflow capture index%93
Tate DirectAire Floorfloor design loadDirectAire static design loadBolted stringer understructurelbs2500
Tate DirectAire Floorfloor impact loadDirectAire impact load91 kg; bolted stringerlbs200
Tate DirectAire Floorfloor open area pctDirectAire panel open area%68
Tate DirectAire Floorfloor rolling load 10000passesDirectAire rolling load at 10000 passesBolted stringerlbs2000
Tate DirectAire Floorfloor rolling load 10passesDirectAire rolling load at 10 passesBolted stringerlbs2000