Rack Infrastructure Specs: OCP Open Rack V3 Frame

frame depth shelf stop to frame rack cl to manifold cl

Datacenter rack infrastructure specifications — OCP Open Rack V3 frame and busbar dimensions, OCP BBU module and shelf electrical parameters, OCP 48V onboard PSU efficiency and peak load profiles, GE OCP 48V power shelf rectifier efficiency comparison, and Tate raised floor system load and airflow performance data

Electrical Engineeringcomponent type: OCP Open Rack V3 Frame9 rowsPage 2 of 3
component typespec parameterparameter nameunitvalue
OCP Open Rack V3 Frameframe option2 dim a busbar datum pDim A to busbar Datum Pmm593.65
OCP Open Rack V3 Frameframe option2 dim a front doorDim A to front doormm166.6
OCP Open Rack V3 Frameframe option2 dim a shelf stopDim A to shelf stopmm585.09
OCP Open Rack V3 Frameframe option2 inner shelfOption 2 inner shelf widthmm610
OCP Open Rack V3 Frameframe option2 inner shelf inOption 2 inner shelf widthin24.016
OCP Open Rack V3 Frameframe option2 rack edge to busbar dtm bRack edge to busbar Datum Bmm50.13
OCP Open Rack V3 Frameframe paint thicknessNominal paint thicknessµm120
OCP Open Rack V3 Frameframe pitch verticalVertical dimension pitch (OU spacing)mm44.45
OCP Open Rack V3 Frameframe rack cl to manifold clRack CL to manifold CL (reference)mm238.0