Rack Infrastructure Specs: OCP Open Rack V3 Frame
frame depth shelf stop to frame rack cl to manifold cl
Datacenter rack infrastructure specifications — OCP Open Rack V3 frame and busbar dimensions, OCP BBU module and shelf electrical parameters, OCP 48V onboard PSU efficiency and peak load profiles, GE OCP 48V power shelf rectifier efficiency comparison, and Tate raised floor system load and airflow performance data
| component type | spec parameter | parameter name | unit | value |
|---|---|---|---|---|
| OCP Open Rack V3 Frame | frame option2 dim a busbar datum p | Dim A to busbar Datum P | mm | 593.65 |
| OCP Open Rack V3 Frame | frame option2 dim a front door | Dim A to front door | mm | 166.6 |
| OCP Open Rack V3 Frame | frame option2 dim a shelf stop | Dim A to shelf stop | mm | 585.09 |
| OCP Open Rack V3 Frame | frame option2 inner shelf | Option 2 inner shelf width | mm | 610 |
| OCP Open Rack V3 Frame | frame option2 inner shelf in | Option 2 inner shelf width | in | 24.016 |
| OCP Open Rack V3 Frame | frame option2 rack edge to busbar dtm b | Rack edge to busbar Datum B | mm | 50.13 |
| OCP Open Rack V3 Frame | frame paint thickness | Nominal paint thickness | µm | 120 |
| OCP Open Rack V3 Frame | frame pitch vertical | Vertical dimension pitch (OU spacing) | mm | 44.45 |
| OCP Open Rack V3 Frame | frame rack cl to manifold cl | Rack CL to manifold CL (reference) | mm | 238.0 |