Rack Infrastructure Specs: OCP Open Rack V3 Busbar

busbar return engagement length ref to busbar voltage nominal

Datacenter rack infrastructure specifications — OCP Open Rack V3 frame and busbar dimensions, OCP BBU module and shelf electrical parameters, OCP 48V onboard PSU efficiency and peak load profiles, GE OCP 48V power shelf rectifier efficiency comparison, and Tate raised floor system load and airflow performance data

Electrical Engineeringcomponent type: OCP Open Rack V3 Busbar7 rowsPage 3 of 3
component typespec parametermax valuemin valueparameter nametest conditionunitvalue
OCP Open Rack V3 Busbarbusbar return engagement length refReference horizontal length of return bus bar engagementReference dimensionmm27.05
OCP Open Rack V3 Busbarbusbar return leading edge radius maxMaximum radius on return bus bar leading edgemm0.25
OCP Open Rack V3 Busbarbusbar salt spray rust grade min6Minimum rust grade after salt spray testgrade6
OCP Open Rack V3 Busbarbusbar salt spray test durationSalt spray test durationPer ASTM B117-07; rust grade requirement ≥6 per ASTM D610-01hours48
OCP Open Rack V3 Busbarbusbar vertical dist between centers20.3519.65Vertical distance between bus bar centersmm20.00
OCP Open Rack V3 Busbarbusbar vertical position top surface24.523.5Vertical position of top conductive surface from datum Pmm24.00
OCP Open Rack V3 Busbarbusbar voltage nominal48V bus bar nominal voltageV48