Rack Infrastructure Specs: OCP 48V Regulated PSU

psu reg monitor output power accuracy to psu reg signal pin 3 function

Datacenter rack infrastructure specifications — OCP Open Rack V3 frame and busbar dimensions, OCP BBU module and shelf electrical parameters, OCP 48V onboard PSU efficiency and peak load profiles, GE OCP 48V power shelf rectifier efficiency comparison, and Tate raised floor system load and airflow performance data

Electrical Engineeringcomponent type: OCP 48V Regulated PSU10 rowsPage 2 of 3
component typespec parameterparameter nametest conditionunitvalue
OCP 48V Regulated PSUpsu reg monitor output power accuracyRegulated PSU output power monitoring accuracy%±5
OCP 48V Regulated PSUpsu reg monitor output voltage accuracyRegulated PSU output voltage monitoring accuracy%±2
OCP 48V Regulated PSUpsu reg monitor temperature accuracyRegulated PSU temperature monitoring accuracy°C±5
OCP 48V Regulated PSUpsu reg peak 130pct 100msRegulated PSU peak load 130% of TDC duration130% of TDCms100
OCP 48V Regulated PSUpsu reg peak 150pct 50msRegulated PSU peak load 150% of TDC duration150% of TDCms50
OCP 48V Regulated PSUpsu reg peak 175pct 5msRegulated PSU peak load 175% of TDC duration175% of TDCms5
OCP 48V Regulated PSUpsu reg peak 200pct 0pt5msRegulated PSU peak load 200% of TDC duration200% of TDCms0.5
OCP 48V Regulated PSUpsu reg signal pin 1 functionRegulated PSU signal connector pin 1 functionPower Good
OCP 48V Regulated PSUpsu reg signal pin 2 functionRegulated PSU signal connector pin 2 functionPMBus Ground
OCP 48V Regulated PSUpsu reg signal pin 3 functionRegulated PSU signal connector pin 3 functionPMBus Data