Rack Infrastructure Specs: OCP 48V Fixed Ratio PSU

psu fixed monitor output voltage accuracy to psu fixed signal pin 3 function

Datacenter rack infrastructure specifications — OCP Open Rack V3 frame and busbar dimensions, OCP BBU module and shelf electrical parameters, OCP 48V onboard PSU efficiency and peak load profiles, GE OCP 48V power shelf rectifier efficiency comparison, and Tate raised floor system load and airflow performance data

Electrical Engineeringcomponent type: OCP 48V Fixed Ratio PSU8 rowsPage 2 of 2
component typespec parameterparameter nametest conditionunitvalue
OCP 48V Fixed Ratio PSUpsu fixed monitor output voltage accuracyFixed ratio PSU output voltage monitoring accuracy%±2
OCP 48V Fixed Ratio PSUpsu fixed monitor temperature accuracyFixed ratio PSU temperature monitoring accuracy°C±5
OCP 48V Fixed Ratio PSUpsu fixed peak 200pct 100msFixed ratio PSU peak load 200% of TDC durationRequired; 200% of TDCms100
OCP 48V Fixed Ratio PSUpsu fixed peak 250pct 10msFixed ratio PSU peak load 250% of TDC durationRequired; 250% of TDCms10
OCP 48V Fixed Ratio PSUpsu fixed peak 300pct 1msFixed ratio PSU peak load 300% of TDC durationOptional; 300% of TDCms1
OCP 48V Fixed Ratio PSUpsu fixed signal pin 1 functionFixed ratio PSU signal connector pin 1 functionPMBus Address
OCP 48V Fixed Ratio PSUpsu fixed signal pin 2 functionFixed ratio PSU signal connector pin 2 functionPMBus Data
OCP 48V Fixed Ratio PSUpsu fixed signal pin 3 functionFixed ratio PSU signal connector pin 3 functionPMBus Clock