Psychrometric Properties: STD ATM

-20.0 10 to -20.0 90

Psychrometric properties of moist air — humidity ratio, enthalpy, dew point, wet-bulb temperature, and specific volume as functions of dry-bulb temperature and relative humidity; also includes saturation thermodynamic and transport properties (viscosity, thermal conductivity, Prandtl number, density) from ASHRAE 2021 tabulated data

Mechanical Engineeringpressure condition: STD ATM10 rowsPage 3 of 23
pressure conditionlookup keydew point C (C)dry bulb C (C)enthalpy kJ kg (kJ/kg)humidity ratio kg kg (kg/kg)relative humidity pct (%)specific volume m3 kg (m3/kg)standardwet bulb C (C)
STD ATM-20.0 10-45.69-20-19.9640.000063100.7172ASHRAE Fundamentals 2017 Ch.1-19.11
STD ATM-20.0 100-22.27-20-18.5570.0006351000.7179ASHRAE Fundamentals 2017 Ch.1-20.27
STD ATM-20.0 20-39.18-20-19.8080.000127200.7173ASHRAE Fundamentals 2017 Ch.1-19.65
STD ATM-20.0 30-35.17-20-19.6510.00019300.7174ASHRAE Fundamentals 2017 Ch.1-19.46
STD ATM-20.0 40-32.22-20-19.4950.000254400.7174ASHRAE Fundamentals 2017 Ch.1-20.23
STD ATM-20.0 50-29.88-20-19.3390.000317500.7175ASHRAE Fundamentals 2017 Ch.1-20.7
STD ATM-20.0 60-27.93-20-19.1820.000381600.7176ASHRAE Fundamentals 2017 Ch.1-20.94
STD ATM-20.0 70-26.25-20-19.0260.000444700.7177ASHRAE Fundamentals 2017 Ch.1-20.99
STD ATM-20.0 80-24.78-20-18.870.000508800.7177ASHRAE Fundamentals 2017 Ch.1-20.88
STD ATM-20.0 90-23.46-20-18.7130.000571900.7178ASHRAE Fundamentals 2017 Ch.1-20.63