Noise Criteria Curves: NC

NC-65#1000 to NC-70#125

Noise Criteria (NC) and Room Criteria (RC) curves for HVAC acoustics design. NC curves per ANSI S12.2-2008 from NC-15 through NC-70 (12 curves), and RC Mark II curves per ASHRAE from RC-25 through RC-50 (6 curves). Each curve has 8 octave band center frequencies (63-8000 Hz) with maximum allowable sound pressure levels in dB. Includes recommended occupancy type and equivalent dBA background noise level. 144 records total.

Mechanical Engineeringcriterion type: NC10 rowsPage 9 of 10
criterion typecurve pointbackground noise dBA equivalent (dBA)max sound pressure level dB (dB)octave band center Hz (Hz)ratingrecommended occupancy
NCNC-65#100075661,000NC-65factory
NCNC-65#1257575125NC-65factory
NCNC-65#200075642,000NC-65factory
NCNC-65#2507571250NC-65factory
NCNC-65#400075634,000NC-65factory
NCNC-65#5007568500NC-65factory
NCNC-65#63758063NC-65factory
NCNC-65#800075628,000NC-65factory
NCNC-70#100080711,000NC-70factory
NCNC-70#1258079125NC-70factory