Noise Criteria Curves: NC

NC-50#4000 to NC-55#500

Noise Criteria (NC) and Room Criteria (RC) curves for HVAC acoustics design. NC curves per ANSI S12.2-2008 from NC-15 through NC-70 (12 curves), and RC Mark II curves per ASHRAE from RC-25 through RC-50 (6 curves). Each curve has 8 octave band center frequencies (63-8000 Hz) with maximum allowable sound pressure levels in dB. Includes recommended occupancy type and equivalent dBA background noise level. 144 records total.

Mechanical Engineeringcriterion type: NC10 rowsPage 7 of 10
criterion typecurve pointbackground noise dBA equivalent (dBA)max sound pressure level dB (dB)octave band center Hz (Hz)ratingrecommended occupancy
NCNC-50#400060484,000NC-50retail
NCNC-50#5006054500NC-50retail
NCNC-50#63607163NC-50retail
NCNC-50#800060478,000NC-50retail
NCNC-55#100065561,000NC-55factory
NCNC-55#1256567125NC-55factory
NCNC-55#200065542,000NC-55factory
NCNC-55#2506562250NC-55factory
NCNC-55#400065534,000NC-55factory
NCNC-55#5006558500NC-55factory