Noise Criteria Curves: NC

NC-40#1000 to NC-45#125

Noise Criteria (NC) and Room Criteria (RC) curves for HVAC acoustics design. NC curves per ANSI S12.2-2008 from NC-15 through NC-70 (12 curves), and RC Mark II curves per ASHRAE from RC-25 through RC-50 (6 curves). Each curve has 8 octave band center frequencies (63-8000 Hz) with maximum allowable sound pressure levels in dB. Includes recommended occupancy type and equivalent dBA background noise level. 144 records total.

Mechanical Engineeringcriterion type: NC10 rowsPage 5 of 10
criterion typecurve pointbackground noise dBA equivalent (dBA)max sound pressure level dB (dB)octave band center Hz (Hz)ratingrecommended occupancy
NCNC-40#100050411,000NC-40office open
NCNC-40#1255056125NC-40office open
NCNC-40#200050392,000NC-40office open
NCNC-40#2505050250NC-40office open
NCNC-40#400050384,000NC-40office open
NCNC-40#5005045500NC-40office open
NCNC-40#63506463NC-40office open
NCNC-40#800050378,000NC-40office open
NCNC-45#100055461,000NC-45restaurant
NCNC-45#1255560125NC-45restaurant