Noise Criteria Curves: NC

NC-25#4000 to NC-30#500

Noise Criteria (NC) and Room Criteria (RC) curves for HVAC acoustics design. NC curves per ANSI S12.2-2008 from NC-15 through NC-70 (12 curves), and RC Mark II curves per ASHRAE from RC-25 through RC-50 (6 curves). Each curve has 8 octave band center frequencies (63-8000 Hz) with maximum allowable sound pressure levels in dB. Includes recommended occupancy type and equivalent dBA background noise level. 144 records total.

Mechanical Engineeringcriterion type: NC10 rowsPage 3 of 10
criterion typecurve pointbackground noise dBA equivalent (dBA)max sound pressure level dB (dB)octave band center Hz (Hz)ratingrecommended occupancy
NCNC-25#400035224,000NC-25hospital
NCNC-25#5003531500NC-25hospital
NCNC-25#63355463NC-25hospital
NCNC-25#800035218,000NC-25hospital
NCNC-30#100040311,000NC-30classroom
NCNC-30#1254048125NC-30classroom
NCNC-30#200040292,000NC-30classroom
NCNC-30#2504041250NC-30classroom
NCNC-30#400040284,000NC-30classroom
NCNC-30#5004035500NC-30classroom