Nec Working Clearances: 9001-25000 V to Above 75000 V
NEC (NFPA 70) working clearance distances — minimum clear distances in front of electrical equipment by voltage range and condition per NEC Table 110.26(A)(1) (0–600 V) and Table 110.34(A) (above 600 V)
| voltage range | condition 1 ft | condition 1 mm (mm) | condition 2 ft | condition 2 mm (mm) | condition 3 ft | condition 3 mm (mm) | nec section | standard |
|---|---|---|---|---|---|---|---|---|
| 9001-25000 V | 5 ft | 1,500 | 6 ft | 1,800 | 9 ft | 2,800 | 110.34(A) | NEC (NFPA 70) 2017 |
| 25001-75000 V | 6 ft | 1,800 | 8 ft | 2,500 | 10 ft | 3,000 | 110.34(A) | NEC (NFPA 70) 2017 |
| Above 75000 V | 8 ft | 2,500 | 10 ft | 3,000 | 12 ft | 3,700 | 110.34(A) | NEC (NFPA 70) 2017 |