Nec Working Clearances: 9001-25000 V to Above 75000 V

NEC (NFPA 70) working clearance distances — minimum clear distances in front of electrical equipment by voltage range and condition per NEC Table 110.26(A)(1) (0–600 V) and Table 110.34(A) (above 600 V)

Electrical Engineeringvoltage_range: 9001-25000 V to Above 75000 V3 rows
voltage rangecondition 1 ftcondition 1 mm (mm)condition 2 ftcondition 2 mm (mm)condition 3 ftcondition 3 mm (mm)nec sectionstandard
9001-25000 V5 ft1,5006 ft1,8009 ft2,800110.34(A)NEC (NFPA 70) 2017
25001-75000 V6 ft1,8008 ft2,50010 ft3,000110.34(A)NEC (NFPA 70) 2017
Above 75000 V8 ft2,50010 ft3,00012 ft3,700110.34(A)NEC (NFPA 70) 2017