Nec Voltage Drop: copper

500 kcmil to 900 kcmil

NEC Chapter 9 Table 8 wire resistance and reactance data — DC resistance, AC resistance, and reactance for copper and aluminum conductors in PVC and steel conduit

Electrical Engineeringconductor material: copper8 rowsPage 3 of 3
conductor materialconductor sizeac reactance ohm per kft pvc (ohm/kft)ac reactance ohm per kft steel (ohm/kft)ac resistance ohm per kft pvc (ohm/kft)ac resistance ohm per kft steel (ohm/kft)area cmil (cmil)dc resistance ohm per kft uncoated (ohm/kft)nec tablestandardstranding
copper500 kcmil0.0390.0480.0270.029500,0000.0258chapter9 table8NEC Chapter 9 Table 837
copper6 AWG0.0510.0640.490.4926,2400.491chapter9 table8NEC Chapter 9 Table 87
copper600 kcmil0.0390.0480.0230.025600,0000.0214chapter9 table8NEC Chapter 9 Table 861
copper700 kcmil700,0000.0184chapter9 table8NEC Chapter 9 Table 861
copper750 kcmil0.0380.0480.0190.021750,0000.0171chapter9 table8NEC Chapter 9 Table 861
copper8 AWG0.0520.0650.780.7816,5100.764chapter9 table8NEC Chapter 9 Table 8solid
copper800 kcmil800,0000.0161chapter9 table8NEC Chapter 9 Table 861
copper900 kcmil900,0000.0143chapter9 table8NEC Chapter 9 Table 861