Sample data from Engineering Database — 375 reference tables, deterministic calculators, and Engineering AI. Sign up free

Nec Voltage Drop: aluminum

2000 kcmil to 500 kcmil

NEC Chapter 9 Table 8 wire resistance and reactance data — DC resistance, AC resistance, and reactance for copper and aluminum conductors in PVC and steel conduit

Electrical Engineeringconductor material: aluminum9 rowsPage 2 of 3
conductor materialconductor sizeac reactance ohm per kft pvc (ohm/kft)ac reactance ohm per kft steel (ohm/kft)ac resistance ohm per kft pvc (ohm/kft)ac resistance ohm per kft steel (ohm/kft)area cmil (cmil)dc resistance ohm per kft uncoated (ohm/kft)nec tablestandardstranding
aluminum250 kcmil0.0410.0520.0850.086250,0000.0847chapter9 table8NEC Chapter 9 Table 837
aluminum3 AWG0.0470.0590.40.452,6200.403chapter9 table8NEC Chapter 9 Table 87
aluminum3/0 AWG0.0420.0520.130.13167,8000.126chapter9 table8NEC Chapter 9 Table 819
aluminum300 kcmil0.0410.0510.0710.072300,0000.0707chapter9 table8NEC Chapter 9 Table 837
aluminum350 kcmil0.040.050.0610.063350,0000.0605chapter9 table8NEC Chapter 9 Table 837
aluminum4 AWG0.0480.060.510.5141,7400.508chapter9 table8NEC Chapter 9 Table 87
aluminum4/0 AWG0.0410.0510.10.1211,6000.1chapter9 table8NEC Chapter 9 Table 819
aluminum400 kcmil0.040.0490.0540.055400,0000.0529chapter9 table8NEC Chapter 9 Table 837
aluminum500 kcmil0.0390.0480.0430.045500,0000.0424chapter9 table8NEC Chapter 9 Table 837