NEC Section 240.6(A) standard overcurrent protective device (OCPD) ratings — standard ampere ratings for fuses and circuit breakers

Electrical Engineeringnec_section: 450.3(A)#circuit_breaker##unsupervised1 row
nec sectionrating ampdescriptiondevice typelocation typenotessecondary protection pcttransformer impedance pct max
450.3(A)#circuit_breaker##unsupervised300Transformer primary OCPD — unsupervised location — % of primary rated currentcircuit_breaker125Unsupervised location; primary CB at 300% primary FLC; secondary OCPD required at 125% secondary FLC (secondary <=1000V) or 250% (secondary >1000V)300unsupervised