Nec Grounding: 250.122

250.122-3000 to 250.122-800

NEC Table 250.122 — minimum equipment grounding conductor sizes based on overcurrent protective device rating

Electrical Engineeringnec table: 250.1229 rowsPage 2 of 2
nec tablerecord idegc alequipment grounding conductor alequipment grounding conductor cuocpd rating A (A)standardtable title
250.122250.122-3000600 kcmil400 kcmil3,000NEC (NFPA 70) Table 250.122Minimum Size Equipment Grounding Conductors
250.122250.122-4001 AWG3 AWG400NEC (NFPA 70) Table 250.122Minimum Size Equipment Grounding Conductors
250.122250.122-4000750 kcmil500 kcmil4,000NEC (NFPA 70) Table 250.122Minimum Size Equipment Grounding Conductors
250.122250.122-5001/0 AWG2 AWG500NEC (NFPA 70) Table 250.122Minimum Size Equipment Grounding Conductors
250.122250.122-50001200 kcmil1200 kcmil700 kcmil5,000NEC (NFPA 70) Table 250.122Minimum Size Equipment Grounding Conductors
250.122250.122-608 AWG10 AWG60NEC (NFPA 70) Table 250.122Minimum Size Equipment Grounding Conductors
250.122250.122-6002/0 AWG1 AWG600NEC (NFPA 70) Table 250.122Minimum Size Equipment Grounding Conductors
250.122250.122-60001200 kcmil1200 kcmil800 kcmil6,000NEC (NFPA 70) Table 250.122Minimum Size Equipment Grounding Conductors
250.122250.122-8003/0 AWG1/0 AWG800NEC (NFPA 70) Table 250.122Minimum Size Equipment Grounding Conductors