Nec Cable Ampacity: correction ambient temp

58 to 83

NEC (NFPA 70) cable ampacity ratings — allowable current for copper and aluminum conductors at 60/75/90°C insulation ratings in raceways and free air; high-temperature conductor ampacity at 150/200/250°C; ambient temperature correction factors; conductor fill adjustment factors

Electrical Engineeringconductor material: correction ambient temp6 rowsPage 2 of 2
conductor materialconductor sizeambient temp Cfactor 75Cfactor 90Cnec tablestandard
correction ambient temp58580.580.71310.15(B)(1)NEC (NFPA 70) Table 310.15(B)(1)
correction ambient temp63630.470.65310.15(B)(1)NEC (NFPA 70) Table 310.15(B)(1)
correction ambient temp68680.330.58310.15(B)(1)NEC (NFPA 70) Table 310.15(B)(1)
correction ambient temp73730.5310.15(B)(1)NEC (NFPA 70) Table 310.15(B)(1)
correction ambient temp78780.41310.15(B)(1)NEC (NFPA 70) Table 310.15(B)(1)
correction ambient temp83830.29310.15(B)(1)NEC (NFPA 70) Table 310.15(B)(1)