Lv Circuit Breaker Specs: Eaton_Magnum_PDSB_5000A_DoubleNarrow_85kA
Vendor-specific product data for low-voltage power circuit breakers (LVPCBs) used in datacenter and industrial switchgear. Covers Eaton Magnum PXR and PD-SB series and Schneider Electric MasterPact MTZ series: catalog numbers, frame ampere ratings, interrupting capacities at 254/508/635 Vac, short-time withstand ratings, fixture dimensions, weights, altitude derating factors, maintenance endurance cycle counts, and trip unit configurations with communication options.
| manufacturer frame | spec type | available in ratings a | catalog number | fixed inst trip peak ka (kA) | frame size a (A) | frame type | interrupting capacity ka 254v (kA) | interrupting capacity ka 508v (kA) | interrupting capacity ka 635v (kA) | manufacturer | poles | series | short time withstand ka 254 508v (kA) | short time withstand ka 635v (kA) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Eaton_Magnum_PDSB_5000A_DoubleNarrow_85kA | frame_ratings | 800,1200,1600,2000,2500,3200,3600,3800,4000,5000 | SPN-85N | 127 | 5,000 | Double Narrow | 85 | 85 | 85 | Eaton | 3 | Magnum PD-SB | 85 | 127 |
This is a sample. Search the full lv circuit breaker specs dataset and 350+ more by creating a free account and accessing the database.
Get started for FREERelated data
Eaton_Magnum_PXR_800A_Narrow_42kA1 rowEaton_Magnum_PXR_800A_Standard_50kA1 rowEaton_Magnum_PXR_1200A_Narrow_50kA1 rowEaton_Magnum_PXR_1200A_Standard_85kA1 rowEaton_Magnum_PXR_1600A_Narrow_100kA1 rowEaton_Magnum_PXR_2000A_Narrow_65kA1 rowEaton_Magnum_PXR_2500A_Standard_65kA1 rowEaton_Magnum_PXR_3000A_Standard_100kA1 rowEaton_Magnum_PXR_4000A_DoubleNarrow_85kA1 rowEaton_Magnum_PXR_5000A_DoubleNarrow_85kA1 rowEaton_Magnum_PXR_6000A_Double_100kA1 rowEaton_Magnum_PDSB_800A_Standard_42kA1 row