Lv Circuit Breaker Specs: Eaton Magnum PDSB 2500A Standard 100kA
Vendor-specific product data for low-voltage power circuit breakers (LVPCBs) used in datacenter and industrial switchgear. Covers Eaton Magnum PXR and PD-SB series and Schneider Electric MasterPact MTZ series: catalog numbers, frame ampere ratings, interrupting capacities at 254/508/635 Vac, short-time withstand ratings, fixture dimensions, weights, altitude derating factors, maintenance endurance cycle counts, and trip unit configurations with communication options.
| manufacturer frame | spec type | available in ratings a | catalog number | fixed inst trip peak ka (kA) | frame size a (A) | frame type | interrupting capacity ka 254v (kA) | interrupting capacity ka 508v (kA) | interrupting capacity ka 635v (kA) | manufacturer | poles | series | short time withstand ka 254 508v (kA) | short time withstand ka 635v (kA) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Eaton Magnum PDSB 2500A Standard 100kA | frame ratings | 200,250,300,400,600,800,1000,1200,1600,2000,2500 | SPS-C25 | 64 | 2,500 | Standard | 100 | 100 | 100 | Eaton | 3,4 | Magnum PD-SB | 42 | 64 |