Lmtd Correction Factors: 2-8

805 to 1006

LMTD correction factors (F) for heat exchangers — shell-and-tube (1-2, 1-4, 1-6, 2-4, 2-8) and crossflow arrangements at various R and P values

Mechanical Engineeringflow arrangement: 2-810 rowsPage 4 of 6
flow arrangementR P keyF factorP valueR valuehx typeshell passestube passes
2-88050.97160.50.8shell and tube28
2-88060.93970.60.8shell and tube28
2-88070.86240.70.8shell and tube28
2-88080.55660.80.8shell and tube28
2-81,0010.99950.11shell and tube28
2-81,0020.99740.21shell and tube28
2-81,0030.99230.31shell and tube28
2-81,0040.98110.41shell and tube28
2-81,0050.95670.51shell and tube28
2-81,0060.89740.61shell and tube28