Sample data from Engineering Database — 375 reference tables, deterministic calculators, and Engineering AI. Sign up free

Lmtd Correction Factors: 1-6

2002 to 4002

LMTD correction factors (F) for heat exchangers — shell-and-tube (1-2, 1-4, 1-6, 2-4, 2-8) and crossflow arrangements at various R and P values

Mechanical Engineeringflow arrangement: 1-66 rowsPage 5 of 5
flow arrangementR P keyF factorP valueR valuehx typeshell passestube passes
1-62,0020.97170.22shell and tube16
1-62,0030.88290.32shell and tube16
1-63,0010.9920.13shell and tube16
1-63,0020.9350.23shell and tube16
1-64,0010.98760.14shell and tube16
1-64,0020.81350.24shell and tube16