Sample data from Engineering Database — 375 reference tables, deterministic calculators, and Engineering AI. Sign up free

Lmtd Correction Factors: 1-4

402 to 603

LMTD correction factors (F) for heat exchangers — shell-and-tube (1-2, 1-4, 1-6, 2-4, 2-8) and crossflow arrangements at various R and P values

Mechanical Engineeringflow arrangement: 1-410 rowsPage 2 of 5
flow arrangementR P keyF factorP valueR valuehx typeshell passestube passes
1-44020.99640.20.4shell and tube14
1-44030.99020.30.4shell and tube14
1-44040.97850.40.4shell and tube14
1-44050.95720.50.4shell and tube14
1-44060.91650.60.4shell and tube14
1-44070.82830.70.4shell and tube14
1-44080.48260.80.4shell and tube14
1-46010.99880.10.6shell and tube14
1-46020.99430.20.6shell and tube14
1-46030.98410.30.6shell and tube14

What else is in Engineering Database

Related data