Sample data from Engineering Database — 375 reference tables, deterministic calculators, and Engineering AI. Sign up free

Lmtd Correction Factors: 1-2

1001 to 2001

LMTD correction factors (F) for heat exchangers — shell-and-tube (1-2, 1-4, 1-6, 2-4, 2-8) and crossflow arrangements at various R and P values

Mechanical Engineeringflow arrangement: 1-210 rowsPage 4 of 5
flow arrangementR P keyF factorP valueR valuehx typeshell passestube passes
1-21,0010.99790.11shell and tube12
1-21,0020.98950.21shell and tube12
1-21,0030.96850.31shell and tube12
1-21,0040.92070.41shell and tube12
1-21,0050.80130.51shell and tube12
1-21,5010.99670.11.5shell and tube12
1-21,5020.98190.21.5shell and tube12
1-21,5030.93870.31.5shell and tube12
1-21,5040.80330.41.5shell and tube12
1-22,0010.99540.12shell and tube12

What else is in Engineering Database