Immersion Cooling Fluids: Shell Immersion S5 X

Physical, thermal, electrical, environmental, and safety properties of immersion cooling and dielectric fluids for datacenter single-phase and two-phase liquid immersion cooling — 3M Novec 649, 3M Novec 7100, 3M Novec 7200, and Shell Immersion S5 X

Mechanical Engineeringfluid_name: Shell Immersion S5 X1 row
fluid nameproperty categoryapplicationautoignition temperature c (C)breakdown voltage kv (kV)chemical namecolor sayboltdc resistivity conditiondc resistivity t ohm m (T·Ohm·m)density conditionfire point coc c (C)flash point c (C)fluid typekinematic viscosity mm2 s (mm2/s)liquid density kg m3 (kg/m3)manufacturermaterial compatibility notesneutralisation value mg koh godp (dimensionless (CFC-11 equivalent))pour point c (C)relative permittivity (dimensionless)specific heat conditionspecific heat j kg k (J/(kg·K))thermal conductivity conditionthermal conductivity w m k (W/(m·K))total sulphur mg kgviscosity condition
Shell Immersion S5 Xphysical_propertiessingle-phase immersion cooling of data center servers35542GTL isoparaffinic hydrocarbon (Fischer-Tropsch synthesis)+30@60°C9.9@15°C220200hydrocarbon (GTL isoparaffin)9.8806ShellNo specific compatibility list in TDS v1.5. GTL isoparaffins are typically compatible with PTFE and Viton/FKM; EPDM may swell moderately; confirm elastomer, polymer, and metal compatibility with Shell for specific system BOM before deployment.<0.010-362.02@40°C2,274@40°C0.142<1@40°C

This is a sample. Search the full immersion cooling fluids dataset and 350+ more by creating a free account and accessing the database.

Get started for FREE

Related data