Hydronic Pipe Capacity: copper_type_L

Hydronic system pipe capacity data — maximum recommended flow rate (GPM), velocity, friction loss, and inside diameter for closed-loop HVAC hydronic systems by pipe material and nominal size

Civil Engineeringpipe_material: copper_type_L3 rows
pipe materialnominal size infriction loss ft per 100ft (ft/100ft)inside diameter in (in)max recommended gpm (gpm)notespipe roughness ft (ft)velocity at max gpm fps (fps)
copper_type_L0.59.20.5452Type L copper; max velocity 4-5 fps for closed loop; ASHRAE/ASPE guideline0.0000054.9
copper_type_L0.757.60.78543/4-in type L copper; standard for terminal unit piping0.0000055.2
copper_type_L113.51.02581-in type L copper; branch circuit range0.0000059.6

This is a sample. Search the full hydronic pipe capacity dataset and 300+ more by creating a free account and accessing the database.

Get started for FREE