Explore the Engineering Database more efficiently by signing up for free. Sign up free

Gg-500v-160-630 — IEC gG

Fuse Class
IEC gG
Record Id
Gg 500v 160 630
Amp Rating Max (A)
630
Amp Rating Min (A)
160
Application
IEC gG 500VAC 160-630A; Larger Nh Fuse Sizes NH2/NH3/NH4; Feeder and Distribution protection; 160A Melting I2t Typ 5000-8000 A2s; 400A Melting I2t Typ 30000-60000 A2s; 630A Melting I2t Typ 80000-120000 A2s
Conventional Fusing Current Factor (dimensionless)
1.6
Conventional Nonfusing Current Factor (dimensionless)
1.1
Current Limiting
Current Limiting
Dimensions Ferrule Blade
Knife Blade Nh Large
Fuse Type
gG
Interrupting Rating kA AC (kA)
120
Rejection Feature
None
Standard
IEC 60269-2
Time Delay
Full Range
Voltage Rating V (V)
500

Source: IEC_60269-2

IEC_gG — record id gg_500v_160_630 · application IEC gG 500VAC 160-630A; larger NH fuse sizes NH2/NH3/NH4; feeder and… · dimensions ferrule blade knife_blade_NH_large · amp rating max 630 A · amp rating min 160 A | Fuse Characteristics | Engineering Database