T300-Lt-1200A — Class T

Fuse Class
Class T
Record Id
T300 Lt 1200A
Amp Rating Label
1200A
Amp Rating Max (A)
1,200
Amp Rating Min (A)
1,200
I2T 100kA A2s (A2s)
3,500,000
I2T 200kA A2s (A2s)
4,000,000
I2T 50kA A2s (A2s)
3,500,000
Peak Lt 100kA a (A)
65,000
Peak Lt 200kA a (A)
80,000
Peak Lt 50kA a (A)
50,000
Standard
IEEE Std 3004.3-2020
Voltage Rating V (V)
300

Source: IEEE Std 3004.3-2020