T-300v — Class T

Fuse Class
Class T
Record Id
T 300v
Amp Rating Max (A)
1,200
Amp Rating Min (A)
0.1
Application
Class T 300VAC 0.1-1200A; Very Compact Physical Size vs Class J/L; Dimensionally Non-interchangeable; Preferred for Service Entrance and Large Feeder Protection Where Space Is Limited
Conventional Fusing Current Factor (dimensionless)
1.35
Conventional Nonfusing Current Factor (dimensionless)
0.9
Current Limiting
Current Limiting
Dimensions Ferrule Blade
Very Compact Ferrule Or Blade
Fuse Type
T
Interrupting Rating kA AC (kA)
200
Interrupting Rating kA DC (kA)
100
Rejection Feature
None Physically Distinct
Standard
Ul 248-15
Time Delay
Fast Acting
Voltage Rating V (V)
300

Source: UL_248-15