K5-600v — Class K

Fuse Class
Class K
Record Id
K5 600v
Amp Rating Max (A)
600
Amp Rating Min (A)
0.1
Application
Class K5 600VAC; Current-Limiting Without Rejection feature; Same I2t Limiting As RK5 But Fits Class H holders; Lower Current Limitation Than K1; Largely Replaced by Class RK5 in New Designs
Conventional Fusing Current Factor (dimensionless)
1.1
Conventional Nonfusing Current Factor (dimensionless)
0.9
Current Limiting
Current Limiting
Dimensions Ferrule Blade
Ferrule Or Knife Blade Class K
Fuse Type
K5
Interrupting Rating kA AC (kA)
200
Rejection Feature
None
Standard
Ul 248-9
Time Delay
Optional
Voltage Rating V (V)
600

Source: UL_248-9