Explore the Engineering Database more efficiently by signing up for free. Sign up free
J-600v-Td — Class J
- Fuse Class
- Class J
- Record Id
- J 600v Td
- Amp Rating Max (A)
- 600
- Amp Rating Min (A)
- 1
- Application
- Time-Delay Class J (e.g. Bussmann Lpj Littelfuse JTD); Dual element; Passes 500% for 10s minimum; Motor Branch Protection at 600VAC; Recommended for Motor Loads Due to Starting Inrush Tolerance
- Conventional Fusing Current Factor (dimensionless)
- 1.1
- Conventional Nonfusing Current Factor (dimensionless)
- 0.9
- Current Limiting
- Current Limiting
- Dimensions Ferrule Blade
- Ferrule Or Knife Blade
- Fuse Type
- J Time Delay
- Interrupting Rating kA AC (kA)
- 200
- Peak Let Through kA at 100kA (kA)
- 1.35
- Rejection Feature
- Rejection Notch Rejection Blade
- Standard
- Ul 248-8
- Time Delay
- Time Delay
- Voltage Rating V (V)
- 600
Source: UL_248-8