Explore the Engineering Database more efficiently by signing up for free. Sign up free

H-600v — Class H

Fuse Class
Class H
Record Id
H 600v
Amp Rating Max (A)
600
Amp Rating Min (A)
0.1
Application
Class H 600VAC; 10kA Interrupting limit; Must Not Be Used Where Available Fault Current Exceeds 10kA; Cannot Provide Arc-Flash Reduction credit; Replace with Class J Or Rk for Modern Arc-Flash Compliant Designs
Conventional Fusing Current Factor (dimensionless)
1.35
Conventional Nonfusing Current Factor (dimensionless)
0.9
Current Limiting
Non Current Limiting
Dimensions Ferrule Blade
Ferrule Or Knife Blade Class H
Fuse Type
H
Interrupting Rating kA AC (kA)
10
Rejection Feature
None
Standard
Ul 248-6
Time Delay
Optional
Voltage Rating V (V)
600

Source: UL_248-6

CLASS_H — record id h_600v · application Class H 600VAC; 10kA interrupting limit; must not be used where available fault… · voltage rating V 600 V · dimensions ferrule blade ferrule_or_knife_blade_class_H · current limiting non_current_limiting | Fuse Characteristics | Engineering Database