Explore the Engineering Database more efficiently by signing up for free. Sign up free
CC-600v-Td — Class CC
- Fuse Class
- Class CC
- Record Id
- CC 600v Td
- Amp Rating Max (A)
- 30
- Amp Rating Min (A)
- 0.1
- Application
- Time-Delay Class CC; Dual element; 10s at 500%; Used for Small Motor Branch Circuits in IEC-Style machines; NEC 430.52 Compliant at 175% Td Setting
- Conventional Fusing Current Factor (dimensionless)
- 1.35
- Conventional Nonfusing Current Factor (dimensionless)
- 1.1
- Current Limiting
- Current Limiting
- Dimensions Ferrule Blade
- 1.5in X 0.41in Ferrule
- Fuse Type
- CC Time Delay
- Interrupting Rating kA AC (kA)
- 200
- Rejection Feature
- Rejection Ferrule 1.5in Tube
- Standard
- Ul 248-4
- Time Delay
- Time Delay
- Voltage Rating V (V)
- 600
Source: UL_248-4