CC-600v-Td — Class CC

Fuse Class
Class CC
Record Id
CC 600v Td
Amp Rating Max (A)
30
Amp Rating Min (A)
0.1
Application
Time-Delay Class CC; Dual element; 10s at 500%; Used for Small Motor Branch Circuits in IEC-Style machines; NEC 430.52 Compliant at 175% Td Setting
Conventional Fusing Current Factor (dimensionless)
1.35
Conventional Nonfusing Current Factor (dimensionless)
1.1
Current Limiting
Current Limiting
Dimensions Ferrule Blade
1.5in X 0.41in Ferrule
Fuse Type
CC Time Delay
Interrupting Rating kA AC (kA)
200
Rejection Feature
Rejection Ferrule 1.5in Tube
Standard
Ul 248-4
Time Delay
Time Delay
Voltage Rating V (V)
600

Source: UL_248-4