ASHRAE Chapter 15 fenestration U-factors (W/m²·K) for windows, skylights, curtain walls, and doors by glazing configuration and frame type. Covers single through quadruple glazing with air, argon, and krypton fill, low-e coatings at various emissivities, and all major frame materials. Source: ASHRAE Handbook Fundamentals 2021 Tables 4 and 6.

Mechanical Engineeringglazing id: 1710 rowsPage 2 of 3
glazing idframe typegap fillgap mm (mm)glazing categoryglazing typelow e emissivity (dimensionless)low e surfacenum panes (dimensionless)u factor Wm2K (W/(m2·K))
17operable alum no breakair13Double Glazing Low-E13 mm airspace e=0.200.22or323.7
17operable alum thermal breakair13Double Glazing Low-E13 mm airspace e=0.200.22or322.75
17operable insul fiberglass vinylair13Double Glazing Low-E13 mm airspace e=0.200.22or322.07
17operable reinf vinyl alum cladair13Double Glazing Low-E13 mm airspace e=0.200.22or322.44
17operable wood vinylair13Double Glazing Low-E13 mm airspace e=0.200.22or322.34
17skylight alum no breakair13Double Glazing Low-E13 mm airspace e=0.200.22or325.57
17skylight alum thermal breakair13Double Glazing Low-E13 mm airspace e=0.200.22or324.8
17skylight glass only centerair13Double Glazing Low-E13 mm airspace e=0.200.22or322.61
17skylight reinf vinyl alum cladair13Double Glazing Low-E13 mm airspace e=0.200.22or324.56
17skylight wood vinylair13Double Glazing Low-E13 mm airspace e=0.200.22or324.19