Explore the Engineering Database more efficiently by signing up for free. Sign up free
Motor-1983-Ind-LV — Motor
- Equipment Type
- Motor
- Class Code
- Motor-1983-Ind-LV
- Description
- Motor Induction 0-1000 V (1983 survey)
- Failure Rate per Year (failures/year)
- 0.0824
- Failures (count)
- 89
- Mdt Hours (h)
- 15
- Mttr Hours (h)
- 42.5
- Standard
- IEEE Std 3006.8-2018
- Survey
- IEEE 1983 Motor Survey
- Unit Years (unit-years)
- 1,080.3
Source: IEEE Std 3006.8-2018