H15-100 — Damper Assembly

Equipment Type
Damper Assembly
Class Code
H15-100
Description
Damper assembly, Motor
Failure Rate per Year (failures/year)
0.003039
Failures (count)
48
Mdt Hours (h)
0.54
Mtbf Hours (h)
2,882,255
Mttm Hours (h)
0.07
Mttr Hours (h)
28.73
Standard
IEEE Std 3006.8-2018 Table 2
Survey
Usace Prep
Unit Years (unit-years)
15,793.2

Source: IEEE Std 3006.8-2018 Table 2