Duct Fitting Loss Coefficients: wye sym 60 ed5 9

Loss coefficients (C-values) for duct fittings — elbows, tees, wyes, transitions, entries, exits, and specialty fittings per ASHRAE Fundamentals and SMACNA. dP = C * Vp where Vp is velocity pressure at the referenced duct cross-section.

Mechanical Engineeringfitting type: wye sym 60 ed5 91 row
fitting typesize or rangeC0 (dimensionless)ashrae codegeometry notesstandard
wye sym 60 ed5 9all0.32ED5-9ED5-9 Symmetric wye 60-degree; Qb/Qc=0.5 Ab1/Ac=Ab2/Ac=0.482; C branch referenced to branch VpASHRAE Handbook Fundamentals 2021 Ch.21