Sample data from Engineering Database — 375 reference tables, deterministic calculators, and Engineering AI. Sign up free

Duct Fitting Loss Coefficients: wye capped 45 with 45elbow

Loss coefficients (C-values) for duct fittings — elbows, tees, wyes, transitions, entries, exits, and specialty fittings per ASHRAE Fundamentals and SMACNA. dP = C * Vp where Vp is velocity pressure at the referenced duct cross-section.

Mechanical Engineeringfitting type: wye capped 45 with 45elbow1 row
fitting typesize or rangeC0 (dimensionless)ashrae codegeometry notesstandard
wye capped 45 with 45elbowall0.61ED5-6ED5-6 Capped wye 45-degree with 45-degree elbow; Ab/Ac=1; C branch referenced to branch VpASHRAE Handbook Fundamentals 2021 Ch.21