Duct Fitting Loss Coefficients: wye 45 straight reduction sd5 3

branch to main

Loss coefficients (C-values) for duct fittings — elbows, tees, wyes, transitions, entries, exits, and specialty fittings per ASHRAE Fundamentals and SMACNA. dP = C * Vp where Vp is velocity pressure at the referenced duct cross-section.

Mechanical Engineeringfitting type: wye 45 straight reduction sd5 32 rows
fitting typesize or rangeC0 (dimensionless)ashrae codegeometry notesstandard
wye 45 straight reduction sd5 3branch0.5SD5-3SD5-3 Wye 45-degree straight body branch with reduction transition; C branchASHRAE Handbook Fundamentals 2021 Ch.21 Tables 10-11
wye 45 straight reduction sd5 3main0.15SD5-3SD5-3 Wye 45-degree straight body branch with reduction transition; C mainASHRAE Handbook Fundamentals 2021 Ch.21 Tables 10-11