Duct Fitting Loss Coefficients: wye 45 basic sd5 1

branch to main

Loss coefficients (C-values) for duct fittings — elbows, tees, wyes, transitions, entries, exits, and specialty fittings per ASHRAE Fundamentals and SMACNA. dP = C * Vp where Vp is velocity pressure at the referenced duct cross-section.

Mechanical Engineeringfitting type: wye 45 basic sd5 12 rows
fitting typesize or rangeC0 (dimensionless)ashrae codegeometry notesstandard
wye 45 basic sd5 1branch0.7SD5-1SD5-1 Basic wye 45-degree (lowest efficiency wye); C branchASHRAE Handbook Fundamentals 2021 Ch.21 Tables 10-11
wye 45 basic sd5 1main0.15SD5-1SD5-1 Basic wye 45-degree (lowest efficiency wye); C mainASHRAE Handbook Fundamentals 2021 Ch.21 Tables 10-11