Loss coefficients (C-values) for duct fittings — elbows, tees, wyes, transitions, entries, exits, and specialty fittings per ASHRAE Fundamentals and SMACNA. dP = C * Vp where Vp is velocity pressure at the referenced duct cross-section.

Mechanical Engineeringfitting type: wye 30 branch ed5 11 row
fitting typesize or rangeC0 (dimensionless)ashrae codegeometry notesstandard
wye 30 branch ed5 1all0.21ED5-1ED5-1 Wye 30-degree branch; Qb/Qc=0.40 As/Ac=0.510 Ab/Ac=0.413; C branch referenced to branch Vp; value is geometry-dependentASHRAE Handbook Fundamentals 2021 Ch.21