Duct Fitting Loss Coefficients: transition fan outlet rect to round

Loss coefficients (C-values) for duct fittings — elbows, tees, wyes, transitions, entries, exits, and specialty fittings per ASHRAE Fundamentals and SMACNA. dP = C * Vp where Vp is velocity pressure at the referenced duct cross-section.

Mechanical Engineeringfitting type: transition fan outlet rect to round1 row
fitting typesize or rangeC0 (dimensionless)ashrae codegeometry notesstandard
transition fan outlet rect to roundall0.16SD4-2SD4-2 Fan outlet rectangular-to-round transition; 260x310mm outlet to round duct; L=460mmASHRAE Handbook Fundamentals 2021 Ch.21