Duct Fitting Loss Coefficients: tee conical branch tapered sd5 10

branch to main

Loss coefficients (C-values) for duct fittings — elbows, tees, wyes, transitions, entries, exits, and specialty fittings per ASHRAE Fundamentals and SMACNA. dP = C * Vp where Vp is velocity pressure at the referenced duct cross-section.

Mechanical Engineeringfitting type: tee conical branch tapered sd5 102 rows
fitting typesize or rangeC0 (dimensionless)ashrae codegeometry notesstandard
tee conical branch tapered sd5 10branch1.1SD5-10SD5-10 Tee with conical branch tapered into body; C branch referenced to branch VpASHRAE Handbook Fundamentals 2021 Ch.21 Tables 10-11
tee conical branch tapered sd5 10main0.15SD5-10SD5-10 Tee with conical branch tapered into body; C mainASHRAE Handbook Fundamentals 2021 Ch.21 Tables 10-11