Duct Fitting Loss Coefficients: tee conical branch sd5 11

branch to main

Loss coefficients (C-values) for duct fittings — elbows, tees, wyes, transitions, entries, exits, and specialty fittings per ASHRAE Fundamentals and SMACNA. dP = C * Vp where Vp is velocity pressure at the referenced duct cross-section.

Mechanical Engineeringfitting type: tee conical branch sd5 112 rows
fitting typesize or rangeC0 (dimensionless)ashrae codegeometry notesstandard
tee conical branch sd5 11branch0.87SD5-11SD5-11 Tee with conical branch; C branch referenced to branch duct VpASHRAE Handbook Fundamentals 2021 Ch.21 Tables 10-11
tee conical branch sd5 11main0.15SD5-11SD5-11 Tee with conical branch; C main referenced to common duct VpASHRAE Handbook Fundamentals 2021 Ch.21 Tables 10-11