Duct Fitting Loss Coefficients: tee_branch_90

Loss coefficients (C-values) for duct fittings — elbows, tees, transitions, entries and exits per ASHRAE Fundamentals and SMACNA. dP = C * Vp where Vp is velocity pressure.

Mechanical Engineeringfitting_type: tee_branch_901 row
fitting typesize or rangeC0 (dimensionless)descriptiongeometry notes
tee_branch_90all0.9Tee fitting - 90-degree branch takeoff from main ductRight-angle branch from round main; C referenced to branch velocity pressure