Duct Fitting Loss Coefficients: tee_45deg_entry_sd5_12

Loss coefficients (C-values) for duct fittings — elbows, tees, wyes, transitions, entries, exits, and specialty fittings per ASHRAE Fundamentals and SMACNA. dP = C * Vp where Vp is velocity pressure at the referenced duct cross-section.

Mechanical Engineeringfitting_type: tee_45deg_entry_sd5_122 rows
fitting typesize or rangeC0 (dimensionless)ashrae codegeometry notesstandard
tee_45deg_entry_sd5_12branch0.64SD5-12SD5-12 Tee 45-degree entry branch; C_branch referenced to branch duct Vp; highest efficiency tee typeASHRAE Handbook Fundamentals 2021 Ch.21 Tables 10-11
tee_45deg_entry_sd5_12main0.15SD5-12SD5-12 Tee 45-degree entry branch; C_main referenced to common duct Vp; highest efficiency tee typeASHRAE Handbook Fundamentals 2021 Ch.21 Tables 10-11